Paradox 1728 manual
Each time the [ENTER] key is pressed, the keypad will display the next digit in the current section and will continue through all the following sections one digit at a time without changing the programmed values. Not available for sections using the Multiple Feature Select Method.
Configuring the H, V and Keypads V2. Press the desired key [1] to [3]. See below. After two minutes, the keypad exits programming mode. When key [3] is OFF not illuminated , the tamper switch is disabled.
When key [3] is ON illuminated , the tamper switch is enabled. If the keypad has no tamper switch, key [3] will be OFF by default. If the keypad has a tamper switch, key [3] will be ON by default. In installations that require using mostly the expansion inputs, refer to Reassign Keypad Zone 2 section [] option [7] on page 10 and Reassign Zones to Expansion Inputs section [] option [8] on page The Expansion zones need to be enabled in order for Zone Programming to work.
Do not assign inputs from different modules to the same expansion input. Enter one digit from the Zone Definition table. Enter one digit from the Partition Assignment table. Select one or more options from the Zone Options table. Burglary 6 - 24 Hr. In the the on-board zones are zones 01 to 05 and in the the on-board zones are zones 01 to Disabled Disabled Disabled 8 rings 32 sec. Disabled 8 attempts 20 sec. No delay 15 min. This option can also be used to reset smoke detectors.
N Normally Open N. N Normally Closed N. Force arming is not supported by keyswitches. If the pager does not support hexadecimals, use only the digits 0 to 9. Master Code 1 is permanently assigned to partition 1 and can be used to create, modify or delete User Access Codes that are assigned to partition 1.
Master Code 2 is permanently assigned to partition 2 except when partitioning is disabled, Master Code 2 will be assigned to partition 1 and can be used to create, modify or delete User Access Codes that are assigned to the same partition. Default for all user codes is options [1], [3] and [4] ON. Therefore, if you add or replace a module you can re-program the module with the settings saved in the control panel.
The keypads will beep twice every second until the procedure is completed. Insert the Memory Key onto the serial connector labelled KEY on the Spectra control panel to which you wish to download the contents of the memory key to.
Re-apply AC and battery power. When the keypad emits a confirmation beep, remove the Memory Key. Enter section [] to reprogram the modules with the information downloaded from the Paradox Memory Key. Remove AC and battery power from the control panel. Make sure the write protect jumper of the Memory Key is on. As a result, when installing a wireless smoke detector to be used with a Spectra system, the corresponding zone must be programmed as follows: 1.
The zone must be defined as a 24Hr Burglary zone. If using Ademco Contact I. When connected to the bus, the APR3-PGM4 automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly. Modules with the APR- prefix are compatible with Spectra versions 2.
Modules with the APR3- prefix are compatible with Spectra versions 2. When connected to the bus, the APR3-PRT1 automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly. When connected to the bus, InTouch automatically detects which control panel it is connected to and adjusts its internal communication parameters to function accordingly.
Only one InTouch can be connected to each Spectra control panel. Refer to the WinLoad Online Help for more information. Zone Assignment The serial number can be located on the inside of the transmitter or you can use the Serial Number Display feature see page Remote control button controls PGM1.
Remote control button controls PGM2 optional. For more information on how to connect two detection devices, please refer to Double Zone Inputs on page 6.
Doubled Zones series connection. See Figure 17 below for a parallel connection drawing. Figure Parallel Wiring only. A Use a 1k9resistor for the zone input.
A - Control panel terminals Please note that the B - Detector 1 terminals parallel connection B method does not support C - Detector 2 terminals tamper recognition. Use a 2. If a line short occurs or the smoke detector activates, where the system is armed or disarmed, the control panel will generate an alarm.
To define zone 1 as a 2-wire smoke detector input: 1. Define zone 1 as a standard or delayed fire zone see Standard 24Hr. Fire Zone on page 17 and Delayed Fire Zone on page Set zone 1 to recognize 2-wire smoke detectors turn option [8] ON.
Each Spectra control panel supports a maximum of five 2-wire smoke detectors. Therefore, the control panel will not generate an alarm if a zone is breached until the Stay Delay has elapsed.
This feature prevents false alarms by allowing users enough time to disarm their system if a zone is accidentally triggered.
For example, if a user opens an armed window or crosses an armed detector on the way to the kitchen in the middle of the night, the user will have enough time to disarm the system before the alarm is generated. In installations where the user must always Force arm when leaving the protected area, this feature allows users to Force arm without pressing the [FORCE] key before entering their User Access Code.
This cannot be done using keyswitches. Force arming is not supported by keyswitches. This feature is not to be used with UL installations. The control panel will not arm the system until all battery trouble conditions are rectified. The control panel will not arm the system until all tamper trouble conditions are rectified. This feature will not function if the Tamper Recognition Options see page 25 are disabled or whenever the tampered zone is bypassed and the Tamper Bypass Options see page 25 have been enabled.
The Auto-Arming. Any open zones detected when a partition is Auto-Armed will be bypassed regardless of their definition except 24hr. The control panel will enter a second Exit Delay period before arming the system. At this point, Auto-Arming can be cancelled by entering a valid access code. Once the partition has successfully armed, the control panel can transmit the Timed Auto-Arming report code programmed in section []. Example: To automatically arm partition 2 everyday at PM, enable Timed Auto-Arming for partition 2 by turning on option [1] in section [].
Then key in into section []. The Auto-Arming Option described in section 6. Upon arming, the control panel will transmit the No Movement report code if programmed in section []. Regardless of whether the system was successfully armed or not, the control panel will always transmit the No Movement report code if programmed in section [].
Example: To arm partition 1 whenever there is no movement for a period of 4 hours, enable No Movement Auto- arming for partition 1 by turning on the [2] Option in section []. Then in section [] enter 16x15min. If No Movement Auto-Arming is disabled, the control panel can still send the No Movement report code when no movement has been detected for the period specified by the No Movement Timer.
The One-touch Arming features allow users to arm the system without having to enter any access codes. To arm the. If the system is partitioned see page 38 , you must also press the key corresponding to the partition you wish to arm. For more information on the different arming methods, please refer to page User Access code, etc. The Exit Delay applies to all zones in the selected partition.
When enabled, the keypad will beep once every second during the Exit Delay and will beep rapidly during the final 10 seconds of the Exit Delay. Max 60 seconds for UL listed systems. Must be enabled for UL installations. When disabled, the Exit Delay timer will start when a partition is armed with a remote control.
If there are any open zones, the control panel will generate another alarm. In one armed period, the control panel will repeat this sequence the number of times defined by the Recycle Counter.
This option is not permitted on UL systems. In a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A silent alarm will not trigger any bells or sirens, but the system will have to be disarmed. In a disarmed system, it functions the same as Trouble Only setting, except it will also generate an audible alarm.
This means the control panel will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition ignores the bypass definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or wire fault occurs on a bypassed zone. Silent alarm: The control panel emits a confirmation beep and transmits the appropriate Panic report code if programmed in section [].
Fire pulsed alarm: Same as audible operation, except that the BELL output will be pulsed as shown in Figure 14 on page Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1. This prevents an aggressor from disarming the system by remote control during a panic situation. Part 8: Reporting and Dialer settings The following section explains all the features and options that must be programmed in order for your security system to properly report system events to a monitoring station.
When an event e. If a report code was programmed, the control panel will dial the monitoring station telephone number defined by the Event Call Direction feature. When the monitoring station answers, the control panel will transmit the System Account Code, followed by the programmed Report Code. Table into section represents up to 4 events in the system. You do not have to program any report codes. Each section from [] to [] represents a set of up to four specific events and each of these events can be programmed with a separate 1- or 2- digit report code.
To program a 1-digit report code, press the [FORCE] key followed by the desired hexadecimal digit or vice versa. When a specific event occurs, the control panel will attempt to transmit the programmed report code to the monitoring station.
The method of report code transmission is defined by the Reporting Formats see page 31 and the Event Call Direction see page These two items define how and where the report codes are transmitted. For more information, refer Reporting Formats on page The following sub-sections provide a brief description of the events that the control panel can report. When using an access code to arm a partition, the control panel can send the appropriate report code to the monitoring station, identifying which access code was used to arm the partition.
Whenever an access code is used to disarm an armed partition or a partition in alarm, the control panel can send the appropriate report code to the monitoring station, identifying which access code was used to disarm the partition. The Disarming and the Special Disarming report codes can be transmitted every time a partition is disarmed or only when a partition is disarmed after an alarm see Disarm Reporting Options on page Only reports if Disarming Reporting Options see page 35 are set to always report disarming.
Whenever a zone generates an alarm, the control panel can send the appropriate report code to the monitoring station, identifying which zone generated an alarm.
The control panel can transmit these report codes to the monitoring station identifying which zone was restored. A zone is restored when it closes after generating an alarm or once the bell has cut-off after alarm generation. Please refer to Zone Restore Report Options on page Whenever a tamper or wire fault occurs on a zone, the control panel can send the appropriate report code to the monitoring station identifying which zone was tampered.
Whenever a tampered zone is restored, the control panel can send the appropriate report code to the monitoring station identifying which zone has been restored.
If Tamper Recognition see page 25 is disabled, the control panel will not report the occurrence of any tampers, wire faults or tamper restores. Transmission of this report code can be delayed see Power Failure Report Delay on page The report code will be transmitted upon the next successful attempt.
You can enter any digit from 0 to 9 and any special keys or functions see Table 6 up to a maximum of 32 digits.
For more information on how these telephone numbers are used, please refer to Event Call Direction on page 32 and Reporting Formats on page After the Maximum Dialing Attempts see page 33 to one monitoring station telephone number have failed, the control panel will then dial the backup telephone number.
If the Alternate Dial Option see page 34 is enabled, the control panel will dial the programmed backup telephone number after every failed attempt. If no backup telephone number is programmed, the control panel will never report to the backup telephone number. Also refer to Delay Between Dialing Attempts on page Partition account numbers can be any hexa-digit from 1 to F. To enter a 3-digit account number, simply press the [FORCE] key followed by the 3-digit account number.
Also, when using 3-digit account numbers, you must use 1-digit report codes. The first digit entered into section [] represents the reporting format used to communicate with Monitoring Station Telephone Number 1, the second digit represents the reporting format used to communicate with Monitoring Station Telephone Number 2. Table 7: Reporting Formats. If the pager does not support Hexadecimals, use only the digits 0 to 9.
This communicator format also uses a pre-defined list of industry standard messages and report codes that will suit most of your basic installation needs. When using the All Codes format, the control panel will automatically generate Contact ID Report Codes for every event in sections [] to []. When using the Ademco Contact ID Programmable format, both telephone numbers must use this reporting format. Since the control panel cannot confirm whether the transmission was successful or not, it can be programmed to call the pager or cellular telephone up to four times and transmit the report codes each time.
To ensure that the report is received, the control panel transmits the account number, the report code and the sign four times during each call.
Also, refer to the Pager Delay in section 8. With option [8] ON, the control panel immediately transmits personal dialing the report code s to a pager or a cellular telephone. The Pager delay in section [] becomes the length of time that the control panel will continue to transmit the report code s to a pager or a cellular phone, giving someone a chance to answer and hear the call.
With option [8] OFF, the control panel will transmit the report code s to a pager or cellular telephone only after the Pager Delay has elapsed.
This feature determines where each group of events will be reported. The control panel events are divided into five groups see above where each event group can be programmed to dial one or both Monitoring Station Telephone Numbers. When a reportable event occurs in the system, the control panel will verify that one of the two telephone numbers has been enabled.
The control panel will begin by dialing the selected telephone number s. If both numbers were selected it will begin with Monitoring Station Telephone Number 1.
Also, refer to Delay Between Dialing Attempts on page Example: The system is armed and zone 1 has been breached causing an alarm. If option [3] is off and option [4] is on in section [], the control panel will attempt to communicate with Monitoring Station Telephone Number 2 in order to transmit the Zone 1 Alarm Report Code programmed in section []. Pulse Ratio of Although most European countries use the pulse ratio, the The same applies for North American countries.
If the With option [4] on, the control panel will dial the backup telephone number after every failed attempt. Use the hour clock to program the time i. The first Test Report will be transmitted within 24 hours after the feature is enabled at the time programmed in []. Example: The Closing Delinquency Timer for partition 1 in section [] is programmed for days. Spectra verifies when partition 1 was last disarmed at midnight everyday.
With option [1] on, the control panel will send the Disarming report codes to the monitoring station when the system is disarmed following an alarm. With option [6] on, the control panel will send the Zone Alarm Restore report codes to the monitoring station as soon as the zone returns to normal or when the system is disarmed. These will be restored when the control panel detects the telephone line again. Please note that when the dialer detects an incoming call, the TLM test will stop for 1 minute.
When a PGM opens, the circuit opens from ground, therefore, cutting power to any devices connected to it. PGM1 A programmable output that provides up to mA. Refer to PGMs for on page 5. PGM2 A programmable output that provides up to mA. PGM2 is designed to be used as a Strobe Output.
If using the PGM Delay, these sections can be used as a second activation event. If a PGM Delay is programmed, the deactivation event can be used as a second activation event. You can program each PGM output to be normally open N.
Otherwise, it will provide a steady output. Also, the event buffer will not be erased. To perform a power down reset: 1 Make sure the Installer Lock is disabled see below 2 Remove battery and AC power from the control panel.
Performing a hardware reset will not affect the current panel settings. To remove the Installer Lock, enter Please note that four seconds after resetting the control panel the STATUS LED on the control panel will flash fast for 5 seconds to indicate that the installer lock is enabled.
Program the duration of the Keypad Lockout from to minutes into section []. If is programmed in section [], the keypads will not be locked-out, but the report code programmed in section [] will be sent. The backup battery can only be recharged at mA if connected to a control panel.
When partitioned, each zone, each User Code see User Code Options on page 11 and some of the system's features can be assigned to Partition 1, Partition 2 or both see Zone Partition Assignment on page If the system is not partitioned, all User Codes and features will be recognized as belonging to Partition 1.
If the system is not partitioned, all zones, User Codes, and features will be recognized as belonging to partition 1. Zones that have been manually assigned to partition 2 will no longer function. Example: If a control panel loses 4 minutes per month, this represents an average loss of 8 seconds per day. Therefore, programming plus 8 seconds into section [] would compensate for the 8-second loss. If Keypad 1 Tamper Supervision is enabled, the control panel will verify the tamper status of the keypad with its Keypad Zone set as keypad zone 1.
If Keypad 2 Tamper Supervision is enabled, the control panel will verify the tamper status of a keypad with its Keypad Zone set as keypad zone 2. For more information on LCD. Regardless of whether the keypad zones are being used or not, if more than one keypad is set with the same keypad zone number, Keypad Tamper Supervision will be lost for that keypad zone.
For example, if two of the keypads in your system have the keypad zones defined as keypad zone 1, the control panel will not recognize a Keypad 1 Tamper Supervision Failure. If a keypad tamper occurs, the control panel can transmit the appropriate Zone Tamper report code see page 29 as originating from the zones specified by the Table 8. If the zone as specified by Table 8 below is enabled, the control panel will report the tamper as originating from the partition where the zone is assigned.
If the zone is not enabled, the control panel will send the Zone Tamper report code as originating from partition 1. The intermittent beeps will re-initialize whenever a new trouble occurs or the trouble restores and re-occurs. Confidential Mode is activated by enabling option [1]. Option [2] regulates whether the keypads will be activated at the touch of a key or only when an access code is entered. Option [3] determines the amount of time without action before the system enters Confidential Mode 5 seconds or 2 minutes.
The keypad will emit a confirmation beep. To disable this mode, press the [TBL] key again. The keypad will emit a rejection beep. When it occurs on in an armed system, the control panel will follow the zone's Alarm Types setting see page In an armed system, the control panel will follow the zone's Alarm Types setting see page Please note that the Wireless Transmitter Supervision Options see section The control panel will not arm any partition until all Supervision Loss trouble conditions are rectified.
This means the control panel will not perform any action if a Supervision Loss occurs on a bypassed zone. When this feature is disabled, the Wireless Transmitter Supervision Options will ignore the bypass definition. This means the control panel will generate an incident as per Wireless Transmitter Supervision Options if a supervision loss occurs on a bypassed zone. Therefore, if you add or replace a module or when you have downloaded the contents of the Paradox Memory Key see Programming Using A Paradox Memory Key on page 10 , you can reprogram the modules with the settings saved in the control panel.
The keypad will emit 2 beeps every second while downloading. Using the WinLoad software you will call the control panel, hang up, then call back.
If the installation site is called back within the programmed delay period, the control panel will override the answering machine or service by picking-up the line after the first ring on the second call. You must wait at least 10 seconds before attempting the second call, otherwise, the control panel will think it is the same call.
Example: A security installation is using an answering machine set to answer after three rings. If section [] has been programmed with 40 seconds and the second call is made within 40 seconds, the control panel will pick up the line on the first ring. If it takes more than 40 seconds, the control panel will not answer on the first ring and the answering machine will answer after three rings.
If the line is not answered after the number of programmed rings, the control panel will answer the call.
You must wait at least 10 seconds before attempting the second call or the control panel will think it is the same call. The control panel will verify that the Panel Identifier in the WinLoad software is the same. If the codes do not match, the control panel will not establish communication.
Therefore, be sure to program the same panel identifier into both the Spectra control panel and the WinLoad software.
If the passwords do not match, the WinLoad software will not establish communication. Wireless Transmitter Supervision Options ReProgram All Expansion Modules Settings for WinLoad Software Panel Answer Options Panel Identifier PC Password PC Telephone Number Call WinLoad Software Answer WinLoad Software Auto Event Buffer Transmission Call Back WinLoad User Operation Trouble Display Programming Access Codes Regular Arming Stay Arming Instant Arming Force Arming Manual Bypass Programming Keyswitch Arming Panic Alarms Alarm Memory Display Programming Chime Zones Keypad Muting Keypad Backlight H and V only Transformer Requirements Table Current Consumption Table Decimal and Hexadecimal Programming Table Zone Recognition Table Special Keys for Telephone Numbers Trouble List All zones, the keyswitches and all user codes are assigned to specific partitions, which makes this a true partitioned system.
Each of these event groups can be programmed with a separate dialing sequence. For example, if zone 5 is open, the [5] key turns on. What could be simpler? Designed to be compatible with any Spectra Series control panel, our Eurostyle Spectra keypads eliminate stocking and ordering concerns.
Designed to be compatible with any Spectra Series control panel, this ergonomic and user-friendly keypad will complete any installation. Most messages in the LCD keypad are programmable. The events can be sent to a dot matrix printer or can be viewed and printed from a computer. Includes a 50mA PGM output. Modules with the APR3prefix are compatible with Spectra versions 2. A second 5A programmable relay PGM is available as an option.
In areas where security system monitoring is not available, let the sophisticated Paravox voice dialer take over.
Compatible with any control panel, the Paravox will verbally report system status by phone, advising of detection of burglary, fire, flood or any other situation programmed to generate a report condition. Fully programmable over the telephone no external keypad required , the Paravox guides the end user through all system functions with a full set of voice prompts. All the user needs to remember is their P. False alarms are virtually eliminated.
With the Digigard 70, animal lovers can maximize their security protection. Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet and prepare them for connection before mounting the circuit board into the back of the cabinet. Select an installation site that isn't easily accessible to intruders and leave at least 2in.
The installation site should be dry and close to an AC source, ground connection and telephone line connection. Connect the zone and dialer ground terminals from the control panel to the metallic enclosure and cold water pipe or grounding rod as per local electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in Figure 2.
For UL installations, the metallic enclosure must be grounded to the cold water pipe. Do not use any switch-controlled outlets to power the transformer. Connect the transformer as shown in Figure 2. Use Table 1 to determine the required transformer. Use a 7Ah battery to comply with UL fire requirements.
Connect the backup battery after applying AC power. When installing verify proper polarity as reversed connections will blow the battery fuse. Also, refer to Battery Charge Current on page The auxiliary power supply terminals can be used to power motion detectors, keypads and other modules or accessories in the security system.
A fuseless circuit protects the power supply against current overload and automatically shuts down if the current exceeds 1. Therefore, the combined current consumption of devices connected to the auxiliary power supply should not exceed mA. If the auxiliary output is overloaded and is shut down, you must disconnect all loads from the output for at least 10 seconds before reconnecting any load back to the auxiliary output.
Modules with the APRprefix are compatible with Spectra versions 2. In order to report system events to the central station, you must connect the incoming telephone company wires into the TIP and RING connections of the control panel and then run the wires from T1 and R1 to the telephone or telephone system as shown in Figure 2. The bell output supplies 12VDC upon alarm and can support one watt or two watt sirens. The bell output uses a fuseless circuit and will automatically shut down if the current exceeds 3A.
When connecting sirens, please verify correct polarity. PGM1 provides a maximum mA output. If the current draw on the PGM is to exceed the current output, we recommend the use of a relay as shown in Figure The PGMs are limited by the power source being used. If it is powered by an external device, PGMs can supply 1A. If the current draw on the PGM is to exceed the current output, we recommend using a relay see Figure 2. This relay can be connected as shown in Figure 2.
Detection devices such as motion detectors and door contacts are connected to the control panel's zone input terminals. Figure 2. Once connected, the associated zone's parameters must be defined. For details refer to Zone Programming on page Enabling the ATZ feature see page 25 on the Spectra or allows you to install two detection devices per input terminal. The ATZ feature is a software oriented feature.
Therefore, there is no need for extra modules. Simply connect the devices as shown in Figure 2. Devices connected to input terminals must be assigned to a zone and the zone's parameters must be defined. Refer to Zone Programming on page 19 for more information. The status of each zone will be displayed on the keypads and the control panel can send separate alarm codes for each zone. There is no limit to the number of keypads that can be connected to the control panel so long as the current consumption does not surpass mA.
For details on Keypad Tamper Supervision see section Each keypad has one zone input terminal, allowing you to connect one motion detector or door contact directly to a keypad.
The keypad can then communicate the status of the zone to the control panel. A maximum of two keypad zones can be used with each control panel. After connecting the device, the zone's parameters must be defined. For details on zone recognition and Zone Programming refer to page Also, refer to the feature Reassign Keypad Zone 2 on page Example: A door contact located at the entry point of an establishment can be wired directly to the input terminal of the entry point keypad instead of wiring the door contact all the way to the control panel.
Keyswitches allow users to arm or disarm a partition by pushing a button or by activating a switch with a key.
0コメント